Actions- Easy Installation: Installation is simplified by the use of a mounting base that may be pre-wired to the system, allowing the detector to be easily installed or removed for maintenance or service. (See Tamper-Resistant Feature/Wiring).
- LED Status Indicators: Two LEDs (green and red) provide local visual indication of the detector’s status – including normal operation, alarm, out of sensitivity and trouble conditions.
- Test button: This button allows the user to perform periodic testing of the detector’s circuitry and verify that the detector is within the sensitivity limits.
- Versatile Mounting: Mounting is made simple with the included hardware and the large mounting ports, which accommodate drywall anchors for easy surface mounting. (See Tamper-Resistant Feature/Wiring).
- Tamper Protection and Tamper Resistance: The detector contains a built-in tamper switch that can communicate back to the control panel in the event the detector is removed from its base. For an added level of security, the detector also includes a tamper resistant element that prevents removal from the base without the use of tools. (See Tamper-Resistant Feature/Wiring).
Item#:
5193SDTA
You must be logged in to order this item.
Log in here
Honeywell's 5808W3 is a 3V lithium powered, photoelectronic smoke/heat detector with a built-in wireless transmitter. It is intended for use with any 5800 Series Wireless Receiver/Transceiver for residential installations (for commercial installations, the 5881ENHC or the 5883H receiver is required).
The transmitter can send alarm, tamper, maintenance (when control panels are equipped to process maintenance signals), and battery condition messages to the system’s receiver. Smoothing algorithms minimize nuisance alarms by smoothing out short term spikes from dust and smoke – virtually eliminating nuisance alarms.
Since there are no holes to drill or wires to run, you can preserve the beauty of the building while protecting it. The 5808W3 is an ideal smoke detector for those difficult to wire locations, applications where room aesthetics are critical, or where hazardous materials exist.
All models also feature a restorable, built-in, fixed temperature (135°F) thermal detector that is also capable of sensing a pre-freeze condition if the temperature is below 41°F.
- Improved Robust RF Field Strength: The distance between the detector and receiver has been significantly increased without the need for a repeater
- Smoothing Algorithms: Mathematical calculations in the detector’s software that minimize nuisance alarms by smoothing out short term spikes from dust and smoke
- Smart Check: A signal is sent to the control panel when the detector requires cleaning. This allows a regular, non-emergency service call to clean the detector before it goes into alarm.
- Drift Compensation: Virtually eliminates nuisance alarms from long-term dust build-up by automatically adjusting the detector’s sensitivity
- Removable Detector Cover and Chamber Top: The technician is able to quickly and easily clean the detector chamber without disassembling the detector head
- Approved UL Listings for Residential and Commercial Applications: Both residential and commercial installation requirements are met
- Additional LED Status Indicators: Identifying between alarm or trouble conditions is a snap with green and red LED status indicators. A green LED denotes a normal condition while the red LED indicates abnormal conditions.
- Easy-to-install Mounting Base: The sturdy mounting base allows the detector to be more easily installed on uneven surfaces (i.e. stucco). The mounting base has larger mounting ports, which accommodate drywall anchors for easy surface mounting.
- Utilizes one long-life 3V lithium battery
- Microcontroller runs on a 4.0 MHz clock
- Horn operates at 3.3 KHz with sound pressure level of 85 dBA at 10 feet
- Built-in wireless transmitter, temporal code 3 sounder
- Maintenance signal fully complies with the sensitivity test requirement specified in NFPA 72, 7-2.2 and is approved by UL